Shunts consist of Manganin rods soldered or silver brazed to brass / copper end blocks. The shunts are artificially aged after manufacture and then tested on full load.
ACCURACY: Class 1.
OVERLOAD:
Shunts are capable of withstanding temperatures upto 120C without any permanent alterations in physical or electrical properties. Overloads and faults which result in temperatures of this magnitude can be safely handled.
All 75 milli volt drop shunts of class 1, withstand the following overload requirements:
2 x rated current for 3 minutes.
4 x rated current for 30 seconds.
10 x rated current for 5 seconds.
TEMPERATURE CO-EFFICIENT:
0.002% per degree centigrate, above ambient temperature in still air, with free ventilation. Temperature not-exceeding 120° C at the centre and 90° C at the ends.
JYINS Shunts are available for current ratings from 5 to 10, 000 AMPS and milli volt drops of 75 milli volts. The shunts confirm to ISI standards IS 1248.
FL-21(5-125A)
Accuracy class
0.5 for 5-4000A
Relative humidity
95%(at 35C)
Working temperature
:-40°C~+60 C
Orerrating capacity
120% of rated current for 2hr
Voltage drop
75mv
Giving out heat when loaded
not be more than 80 after remperature rise
Steady
not be more than 120C at rated current of over 50A